MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

NFPA Standard-Specific Requirements

The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the MS-5UD/MS-10UD may be used to trip any dialer UL listed
for Central Station/Remote Station Reporting Services.

Figure B.1 MS-5UD/MS-10UD FACP Connection to 411UD

Channel1

Channel 2

Channel 3

Channel 4 (2.2K ELR)

Relay Output (DACT Trouble) from 411UD

FACP Supervisory Relay

FACP Alarm Relay

FACP Trouble Relay

J4 Not Installed

411UD

1
2
3
4
5
6
7
8

+ 24 VDC nonresettable power

- 24 VDC nonresettable power

2.2K ELRs P/N 27070

1
2
3
4
5
6
7
8
9

1 2 3 4 5 6 7

FACP

Jumper -VDC to Trouble Relay contact

Trouble Input
(non-supervised,
power-limited)

411UD

FACP

Alarm

TB2-1

TB8-1

TB2-2

TB8-3

Trouble

TB2-3

TB8-4

TB2-4

TB8-6

Supervisory

TB2-5

TB8-7

TB2-6

TB8-9

Table B.1 411UD Connections to FACP