Mounting/installation, Ann-led board layout and connection to facp, 7 ann-rly relay module – Fire-Lite MS-10UD Series FACP User Manual

Page 54: Specifications, Ann-rly relay module

Advertising
background image

54

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Installation

ANN-BUS Devices

Mounting/Installation

Install the ANN-LED Module as described in the documentation supplied with the annunciator.

ANN-LED Board Layout and Connection to FACP

Figure 2.27 illustrates the ANN-LED board wiring connections to the FACP.

2.8.7 ANN-RLY Relay Module

The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compat-
ible FACP.

Specifications

Operating Voltage: 24 VDC

Max. Current:

Alarm: 75 mA

Standby: 15 mA

Relay Contact Ratings:

2 amps @ 30 VDC (resistive)

0.5 amps @ 30 VAC (resistive)

Operating Temperature: 32

o

F to 120

o

F (0

o

C to 49

o

C)

For indoor use in a dry location only

Figure 2.27 ANN-LED Board Layout and Connection to FACP

FACP

ANN-LED

Primary ANN-BUS

+24 VDC

-24 VDC

ANN-BUS (ID#)
Address DIP switch

TB3

an

nl

e

d

to

5x.w