Ann-i/o connection to facp, Ann-i/o module led wiring – Fire-Lite MS-10UD Series FACP User Manual

Page 52

Advertising
background image

52

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Installation

ANN-BUS Devices

ANN-I/O Connection to FACP

The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.25. After the
ANN-I/O is connected to the panel, it must be added to the system via FACP programming.

ANN-I/O Module LED Wiring

There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized so
that there is approximately 10 mA of current for each LED. No series resistors are required. LED
outputs are mapped to output circuits. Refer to the section titled “ANN-I/O LED Zone Assign-
ments” on page 77 of
this manual.

Figure 2.25 ANN-I/O Connection to FACP

ANN-I/O Module

ANN-BUS and power wiring are
supervised and power-limited

TB3

Primary ANN-BUS

an

n-

io

to

5x.w

m

f

Advertising
This manual is related to the following products: