MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

63

Master Programming Level

Programming

While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.

Verification

Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and
not a false alarm. This feature is selected by pressing 3 while viewing the Edit Zone Screen #2 so
that the display reads Verification On. Each time the 3 key is pressed, the display will toggle
between Verification On and Verification Off. For a detailed description, refer to “Alarm Verifica-
tion (None or One Minute)” on page 104.

Note that verification can only be enabled for a zone that is programmed as a smoke detector type.
Zones programmed for any other type will not allow the Verification feature to be enabled. Do not
use the verification feature if a mix of smoke detectors and normally open contact devices are con-
nected to the same zone.

PAS/Pre-Signal Delay

Pressing 1 while viewing Edit Input Zone Screen #3 will display the following screen:

Pre-signal

The Pre-signal option programs the zone to delay panel activation for a preprogrammed time delay
of up to three minutes while allowing for visual verification by a person. Note that the alarm relay
and communicator will respond to the initial alarm immediately. To enable the Pre-signal feature,
press 2 while viewing PAS/Pre-Signal Screen. Refer to “Presignal” on page 102.

PAS

The PAS (Positive Alarm Sequence) option will program the zone to delay panel activation (includ-
ing alarm relay and communicator) for a period of 15 seconds plus a programmable time of up to 3
minutes. To enable the PAS feature, press 3 while viewing the PAS/Pre-Signal Screen. This option
is available only for circuits programmed as smoke detector circuits. Refer to “Positive Alarm

Proc-Mon

Piezo

Procmon-AR

Piezo, nonlatching

AC-Loss-Mon

Trouble

Ack-Switch

Acts like panel Acknowledge Key

Sil-Switch

Acts like panel Alarm Silence Key

Drill-Switch

Acts like panel Drill Key

Reset-Switch

Acts like panel Reset Key

PAS-Bypass

Positive Alarm Sequence Disable

Drill-Switch AutoResettable

Acts like panel Drill Key, nonlatching

Table 3.1 Zone Types

NOTE:

Almost any Input Zone type can activate an ACC-25/50ZST audio zone and output an

assigned message with the exception of ACKNOWLEDGE, SILENCE, RESET and PAS
BYPASS Switches. The DRILL Switch (or input programmed as a drill switch) will cause all of
the corresponding ACC-25/50ZST audio zones to go active and will output Message 1.

INPUT ZONE

1=ENABLED

2=TYPE

3=VERIFICATION

Edit Input Zone Screen #2

INPUT ZONE #

1=PAS/PRE-SIG DELAY

NO DELAY

Edit Input Zone Screen #3

PAS/PRE-SIG DELAY

1=NO DELAY

2=PRE-SIGNAL DELAY

3=PAS DELAY

PAS/Pre-Signal Delay Screen