4 digital alarm communicator/transmitter, 5 components, 6 optional modules and accessories – Fire-Lite MS-10UD Series FACP User Manual

Page 21

Advertising
background image

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

21

Digital Alarm Communicator/Transmitter

Product Description

1.4 Digital Alarm Communicator/Transmitter

Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green Kissoff LED. The integral digital communicator provides the fol-
lowing functions:

Line Seizure: takes control of the phone lines disconnecting any premises phones

Off/On Hook: performs on and off-hook status to the phone lines

Listen for dial tone: 440 Hz tone typical in most networks

Dialing the Central Station(s) number: default is Touch-Tone

®

, programmable to rotary

For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.

Communicate in the following formats:

Ademco Contact ID

SIA-DCS-8

SIA-DCS-20

1.5 Components

Main Circuit Board

The main circuit board contains the system’s CPU, DACT and other primary components and wir-
ing interface connectors. Optional modules plug in and are mounted to the main circuit board.

Power Supply

One power supply is provided standard with each FACP, mounted to a chassis.

FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)

FLPS-7 for the MS-5UD-7(C/E), MS-10UD-7(C/E)

Cabinet

The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050) which mounts inside the cabinet and trim-ring (TR-CE). The Canadian version is supplied
standard with a modified dress panel and one ANN-LED annunciator module.

Batteries

The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.

1.6 Optional Modules and Accessories

CAC-5X Class A Converter Module

The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The
module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS-
10UD. Note that two Class A Converter modules are required for the 10 zone panel.

4XTMF Transmitter Module

The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm condi-
tion exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.

Advertising
This manual is related to the following products: