Programming

Master Programming Level

Auto-Configure

The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online. The software will search for all ANN-BUS modules and automatically
program the device type and address into the system. Pressing 3 while viewing ANN-BUS Screen
#1 will begin the Auto-Configure process and cause the following screen to be displayed:

ANN-S/PG Options Screen

The Printer Option allows the user to configure the optional printer. Pressing 1 while viewing the
ANN-BUS Screen #2 will display the following screens:

Pressing 1 for Port while viewing Printer Options screen #1 will allow the programmer to select
between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause the dis-
play to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that the
interface selected determines which options are available to the user.

If the Parallel Port option is selected, the user has the option to supervise the printer and select an
offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print Options
screen #1. Each press of the 2 key will cause the display to toggle between Printer Supv NO for no
supervision and Printer Supv YES for printer supervision. Note that this option is not selectable if
the Serial Port option has been selected.

If the Parallel Port option is selected, the user has the ability to select an Offline Timer by pressing
3 while viewing Print Options screen #1. The resultant screen allows the programmer to program
the Offline Timer for a delay of between 0 and 255 seconds before loss of printer supervision is
reported as a trouble.

If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be available.
The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the Serial Port
option has been selected.

Pressing 1 for Baud Rate while viewing Printer Options screen #2 will cause a screen to appear
which allow the user to select a Baud Rate of 19200, 9600, or 2400.

Pressing 2 for Data Bits while viewing Printer Options screen #2 will cause screens to appear
which allow the user to select 5, 6, 7, or 8 Data Bits.

Pressing 3 for Parity while viewing Printer Options screen #2 will cause a screen to appear which
allows the user to select between No Parity, Even Parity, or Odd Parity.

Pressing 1 for Stop Bits while viewing Printer Options screen #3 will cause a screen to appear
which allows the user to select between 0.5, 1.0, or 2.0 Stop Bits.

ANN-I/O LED Zone Assignments

The information displayed by LEDs on every ANN-I/O module is not programmable and will
therefore be as indicated in the following table.

LED

Zone (any address)

1

AC Fault

2

General Alarm

3

General Supervisory

ANN-BUS

AUTO-CONGFIGURE

IN PROGRESS

PLEASE WAIT

Auto-Configure Screen

PROGRAMMING

1=ANN-S/PG OPTIONS

2=ANN-80 OPTIONS

3=ANN-RLY OPTIONS

ANN-BUS Screen #2

ANN-S/PG OPTIONS

1=PORT PARALLEL

2=PRINTER SUPV NO

3=OFFLINE TIMER 60

Printer Options Screen #1

ANN-S/PG OPTIONS

1=BAUD RATE N/A

2=DATA BITS N/A

3=PARITY N/A

Printer Options Screen #2

ANN-S/PG OPTIONS

1=STOP BITS N/A

Printer Options Screen #3