MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

77

Master Programming Level

Programming

ANN-80 Options Screen

Pressing 2 while viewing ANN-BUS screen #2 will display the following screen:

The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-80 module will ever sound. Pressing 1 while viewing the ANN-80 Options Screen
#1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.

The Lock Enable option allows the programmer to select whether or not the ANN-80 annunciator
must be unlocked by its key before any annunciator key presses will function. Pressing 2 while
viewing the ANN-80 Options Screen #1 causes the display to toggle between Lock Enable Yes
(annunciator must be unlocked for keys to function) and Lock Enable No (lock position is ignored).

The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 annunciator will function normally or
always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the display to
toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No
(Ack/Step button never functions).

4

General Trouble

5

Alarm Silenced

6

Earth Fault

7

Battery Fault

8

Charger Fault

9

Disable

10

Maintenance

11

Zone 1 Alarm

12

Zone 2 Alarm

13

Zone 3 Alarm

14

Zone 4 Alarm

15

Zone 5 Alarm

16

Zone 6 Alarm

17

Zone 7 Alarm

18

Zone 8 Alarm

19

Zone 9 Alarm

20

Zone 10 Alarm

21

Zone 1 Trouble

22

Zone 2 Trouble

23

Zone 3 Trouble

24

Zone 4 Trouble

25

Zone 5 Trouble

26

Zone 6 Trouble

27

Zone 7 Trouble

28

Zone 8 Trouble

29

Zone 9 Trouble

30

Zone 10 Trouble

31

Zone 1 Supervisory

32

Zone 2 Supervisory

33

Zone 3 Supervisory

34

Zone 4 Supervisory

35

Zone 5 Supervisory

36

Zone 6 Supervisory

37

Zone 7 Supervisory

38

Zone 8 Supervisory

39

Zone 9 Supervisory

40

Zone 10 Supervisory

ANN-80 OPTIONS

1=PIEZO ENABLE

2=LOCK ENABLE

3=ACK BTN ENABLE

ANN-80 Options Screen #1

ANN-80 OPTIONS

1=SIL BTN ENABLE

2=RST BTN ENABLE

3=DRL BTN ENABLE

ANN-80 Options Screen #2