MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Programming

Master Programming Level

Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout, which is blank, to a user defined readout when the control panel is in
Normal condition

Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr),
date and daylight savings time feature into the FACP memory

Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during
a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will
continue to sound at these rates until the alarm or trouble condition is cleared. If the Trouble
Reminder
feature is not enabled and a trouble condition is not cleared within 24 hours, the
panel will reactivate the trouble sounder and retransmit the trouble condition to the central
station if connected

Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to “Canadian Option” on page 74).
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.

Charger Disable: This option allows the programmer to disable the onboard battery charger in
the event an external battery charger is being used

Pressing 1 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:

Timers

Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while
viewing System Setup Screen #1. The following screen will be displayed:

PAS (Positive Alarm Sequence) Delay

The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds
for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following dis-
play will appear:

A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.

PROGRAMMING

1=SYSTEM SETUP

2=OPTION MODULES

3=HISTORY

Programming Screen #2

SYSTEM SETUP

1=TIMERS

2=BANNER

3=TIME-DATE

System Setup Screen #1

SYSTEM SETUP

1=TROUBLE REMIND NO

2=CANADIAN OPTION OFF

3=CHARGR DISABLE NO

System Setup Screen #2

SYSTEM SETUP

1=TIMERS

2=BANNER

3=TIME-DATE

System Setup Screen #1

TIMERS

1=PAS DELAY 120

2=PRE SIGNAL 120

3=WATERFLW DELAY 0

Timer Screen #1

TIMERS

1=AC LOSS DELAY 2

Timer Screen #2

TIMERS

1=PAS DELAY 120

2=PRE SIGNAL 120

3=WATERFLW DELAY 0

Timer Screen #1

PAS DELAY

RANGE 000-180 SECONDS