74

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Programming

Master Programming Level

Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will begin. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 1 will select the fourth week, and 2 will select the
last week of the selected month.

Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the
programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1
will select September, 2 will select October, and 3 will select November.

Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will end. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 4 will select the fourth week, and 5 will select the
last week of the selected month.

Trouble Reminder

The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
alarms and troubles, after the panel has been silenced. Refer to “System Setup” on page 70, for a
detailed description of this feature. Pressing 1 while viewing System Setup Screen #2 will cause
the display to toggle to Trouble Rem Yes, which enables this feature. Each press of the 1 key will
cause the display to toggle between Trouble Rem Yes and Trouble Rem No.

Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for more
than 24 hours will cause the FACP to resound the trouble sounder.

Canadian Option

Pressing 2 while viewing System Setup Screen #2 will configure the FACP to comply with Cana-
dian requirements. The display will change to Canadian Opt. On. Each press of the 2 key will
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory default
setting is Canadian Opt. Off.

For Canadian applications, remote annunciation must be done using the secondary ANN-BUS.

The Canadian Options configures the FACP with the following as required by Canada:

The following zone type codes are not available:

non-latching supervisory

non-latching drill

process monitor (latching or non-latching)

hazard

tornado

medical alert

combo autoresettable

The auto-silence feature can be enabled or disabled. If this feature is enabled, the alarm signals
will be turned off after 20 minutes of activation

The installer must write in the Date of Final Assembly on the Master Marking and Warranty
label, located on the FACP backbox door

Charger Disable

Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or disable
the onboard battery charger. If an external battery charger is being used, the onboard battery char-
ger must be disabled. Each press of the 3 key will toggle between Chrgr Disable No and Chrgr
Disable Yes
.

SYSTEM SETUP

1=TROUBLE REMIND NO

2=CANADIAN OPTION OFF

3=CHARGR DISABLE NO

System Setup Screen #2