Master Programming Level

Programming

Test Time Interval

Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be dis-
played:

The test report sent to the Central Station phone number may be sent once every 6, 8, 12 or 24
hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens
shown above.

Account Code

Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be dis-
played:

The Account Code, which is assigned by a Central Station, depends on the communication format
being used. The Account Code screen will have a flashing cursor in the lower left corner. Program
the supplied 4-digit account code using 0 - 9 and A - F keys. Enter the first digit, then press the
right arrow key to move the cursor to the right, one position. Repeat the process until all digits are
entered.

24 Hour Test Time

Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be dis-
played:

Use the 24 Hour Test Time screen to program the time that the DACT will transmit the 24 Hour
Test to the Central Station. A flashing cursor will appear in the lower left corner of the screen.
Enter a four digit number representing the test time using military time (0000 = midnight and 2359
= 11:59PM).

Phone Number

Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be dis-
played:

The Phone Number screen is used to enter the Central Station phone number that the DACT will be
contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9 and A - C
where A = *, B = # and C = look for secondary dial tone for up to 2 seconds (then dial anyway).

A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press
the right arrow key to move the cursor to the right one position. Enter the second digit and repeat
the process until all digits are entered. Press the Enter key to store the phone number in memory.

CENTRAL STATION

1=TEST TIME INT

2=ACCOUNT CODE

3=24HR TST TIME

Primary/Secondary Screen #1

TEST TIME INTERVAL

1=24 HOURS

2=12 HOURS

3=8 HOURS

Test Time Interval Screen #1

TEST TIME INTERVAL

1=6 HOURS

Test Time Interval Screen #2

ACCOUNT CODE

RANGE 0000-FFFF

Account Codes Screen

CENTRAL STATION

1=TEST TIME INT

2=ACCOUNT CODE

3=24HR T TIME

Primary/Secondary Screen #1

24 HOUR TEST TIME

ENTR USING 24HR TIME

RANGE 0000-2359

24 Hour Test Time Screen

CENTRAL STATION

1=PHONE NUMBER

Primary/Secondary Screen #2

PHONE NUMBER

20 NUMBERS MAXIMUM

Phone Number Screen