2 initial power-up, 3 programming screens description – Fire-Lite MS-10UD Series FACP User Manual

Page 59

Advertising
background image

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

59

Initial Power-up

Programming

Read Status mode can be entered while the panel is in any mode of operation. If an alarm or super-
visory event exists at the panel, the event must be cleared before entering Programming mode. To
access any of the programming or read status features, the Enter or Mode key must be pressed,
which will cause the LCD to display the following:

Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Sta-
tus Mode which allows the user to view the programmed features and status of the control panel
The Read Status feature is not password protected. Refer to “Read Status” on page 105 for a
detailed description of this feature.

Pressing 2 will select user Programming Mode which may only be accomplished by an authorized
person. After pressing 2, a screen will prompt for a password. After entering the correct password,
the user may select from a list of programming options.

Pressing 4 will select Remote Download which allows the user to enable the remote programming
option. Refer to “Remote Download” on page 113.

Exit Programming and Read Status Mode

The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the
display reads System All Normal. Ten minutes of inactivity will also cause the panel to exit Pro-
gramming Mode Note that the data which is entered during Programming mode is not saved until
the programmer exits this mode by repeatedly pressing the ‘ESC’ key. If the Reset key is pressed or
power is lost before exiting Programming mode, all data just entered will be lost.

User Programming Levels

There are two user programming levels:

User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.

User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.

3.2 Initial Power-up

The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.

After completing the wiring of devices to the FACP, apply power to the control panel. If wiring has
not been completed and/or End-of-Line resistors are not installed at the panel, a trouble condition
will be indicated at the panel and a trouble message will be displayed on the LCD. Following is an
example of a possible trouble message that may be displayed.

3.3 Programming Screens Description

Three options are available when the Enter key is pressed: Read Status, Programming, and Remote
Download Mode. The Read Status and Programming options have multiple functions or features
which may be chosen. To view all of the choices, it is necessary that the programmer scroll through

1=READ STATUS MODE

2=PROGRAMMING MODE

3=FUTURE USE

4=REMOTE DOWNLOAD

TROUBLE PULL STATION

ZONE 1 OPEN FAULT

09:03A 090909