Appendix D: Wire Requirements

Connecting external system accessories to the main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, gauge and run length for each cir-
cuit. Reference the chart below to specify wire requirements and limitations for each circuit.

D.1 MS-5UD-3(E) & MS-10UD-3(E) NAC Wiring

The following table lists NAC wiring requirements for the MS-5UD-3(E) & MS-10UD-3(E) FACP
which utilizes the FLPS-3 power supply.

CIRCUIT CONNECTIONS

WIRE REQUIREMENTS

Circuit Type

Circuit Function

Wire Type and

Limitations

Recommended

Max. Distance

Feet (meters)

Wire Gauge

Initiating Device

Circuit

(power-limited)

Connects to Initiating
Devices

Untwisted, unshielded wire
(maximum loop resistance
not to exceed 100 ohms)

Distance limitation
set by 100 ohm
resistance limitation

12-18 AWG (3.25 - 0.75 mm

2

)

ANN-BUS (EIA-485)
power-limited

Communication for
ANN-BUS annunciator
and relay modules

Twisted pair a maximum
loop resistance of 120
ohms

6,000 (1,800 m)

12-18 AWG (3.25 - 0.75 mm

2

)

ANN-BUS Power

Power for ANN-BUS
annunciators

Refer to Table 2.1, “Wiring Distances,” on page 42 for information on device wiring

24 VDC Regulated,
resettable,
nonresettable

Power for accessories
and
4-wire devices

Untwisted, unshielded wire

Distance limitation
set by 4 volt
maximum line drop

12-18 AWG (3.25 - 0.75 mm

2

)

Auxiliary Trouble
Input

Open Collector trouble
input for CHG-75,
CHG-120F, etc.

Single conductor

Distance limitation
20 feet in same
room

18 AWG (0.75 mm

2

)

Remote Sync Output

Provides strobe and
normal sync for
remote NAC power
supplies

Untwisted, unshielded pair
wire

Distance set by 295
ohm resistance
limitation

12-18 AWG (3.25 - 0.75 mm

2

)

NAC Outputs

Connects to NAC
devices or Release
devices

Untwisted, unshielded pair
wire

Refer to Section D.1 and Section D.2 on page 133.

Table D.1 FACP Wire Specifications

NAC Load

(Amps)

Max.

allowable total

loop

resistance

(ohms)

CLASS-B

Max. allowable wire pair length

(feet)

CLASS-A

Max. allowable wire pair length

(feet)

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

0.25

6.00

1554

977

613

386

777

489

307

193

0.5

3.00

777

489

307

193

389

244

153

97

0.75

2.00

518

326

204

129

259

163

102

64

1

1.50

389

244

153

97

194

122

77

48

1.25

1.20

311

195

123

77

155

98

61

39

1.5

1.00

259

163

102

64

130

81

51

32

1.75

0.86

222

140

88

55

111

70

44

28

2

0.75

194

122

77

48

97

61

38

24

2.25

0.67

173

109

68

43

86

54

34

21

2.5

0.60

155

98

61

39

78

49

31

19

Table D.2 NAC Wiring Requirements for FACP with FLPS-3 Power Supply

NOTE: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.