Product Description

Controls and Indicators

1.3 Controls and Indicators

LCD Display

The FACP uses an 80-character (4 lines X 20 characters)
high viewing angle LCD display. The display includes a
long life LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the LED back-
light will turn off to conserve batteries.

Key Panel

Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.

Function keys:

Acknowledge/Step

Alarm Silence

Drill

System Reset (lamp test)

Service/program keys:

Keys labeled 1 to 9

* key

# key

0 (recall) key

1st Event key

Clear key

Escape key

Mode key

Four cursor keys (up, down, left and right)

Enter key

LED Indicators

LEDs are provided to annunciate the following conditions:

Fire Alarm - red LED

Supervisory - yellow LED

AC Power - green LED

System Trouble - yellow LED

Alarm Silence - yellow LED

Primary Phone Line Active (on circuit board) - red LED

Secondary Phone Line Active (on circuit board) - red LED

Kiss-off (on circuit board) - green LED

Local Piezo Sounder

A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process
monitor and supervisory conditions as follows:

Alarm - on steady

Trouble - pulse 1 second on and 1 second off

Maintenance - pulse 1 second on and 1 second off

Supervisory - pulse ½ second on and ½ second off

Process Monitor - pulse ¼ second on and ¼ second off

SYSTEM ALL NORMAL

10:00A 012105

Figure 1.3 Membrane/Display Panel