Master Programming Level

Programming

ANN-AUDIO Options Screen

Pressing 1 for ANN-AUDIO Options while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:

This screen shows the Input Zone that has been assigned to be the All-Call Zone. In this example,
Zone 1 is the All-Call Zone. The All-Call Zone can be changed by pressing the 1 key while view-
ing the ANN-AUDIO Options Screen. The following screens will be displayed.

These screens allow the programmer to select which Input Zone will be assigned as the All-Call
Zone.

ANN-SEC Enable

The ANN-SEC option must be enabled if any modules are connected to the ANN-SEC option card
at J13. To enable the Secondary ANN-BUS, press 2 while viewing ANN-BUS Screen #3 so that the
display reads ANN-SEC ENABLE YES. Each press of the 2 key will cause the display to toggle
between ANN-SEC ENABLE YES and ANN-SEC ENABLE NO. The factory default setting is ANN-
SEC ENABLE NO
.

Onboard DACT

The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a cen-
tral station. Pressing 2 while viewing the Option Module Screen will cause the following screens
to be displayed:

Primary Phone

Press 1 while viewing Onboard DACT Screen to program the type of primary phone line being
connected to the DACT. The following screen will be displayed:

Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33, or 3
to select Rotary dialing with a make/break ratio of 60/40.

PROGRAMMING

1=ANN-AUDIO OPTIONS

ANN-BUS Screen #3

ANN-AUDIO OPTIONS

1=ALL CALL ZONE 1

ANN-AUDIO Options Screen

ANN-AUDIO ALL CALL

1=NO ALL CALL ZONE

2=INPUT ZONE 1

3=INPUT ZONE 2

All-Call Options Screen #1

ANN-AUDIO ALL CALL

1=INPUT ZONE 3

2=INPUT ZONE 4

3=INPUT ZONE 5

All-Call Options Screen #2

ANN-AUDIO ALL CALL

1=INPUT ZONE 9

2=INPUT ZONE 10

All-Call Options Screen #4

(MS-10UD Only)

ANN-AUDIO ALL CALL

1=INPUT ZONE 6

2=INPUT ZONE 7

3=INPUT ZONE 8

All-Call Options Screen #3

(MS-10UD Only)

OPTION MODULES

1=ANN-BUS

2=ON BOARD DACT

Option Module Screen

ANN-BUS

1=ANN-AUDIO OPTIONS

2=ANN-SEC ENABLE NO

ANN-BUS Screen #3

ON BOARD DACT

1=PRIM PHONE TCH TNE

2=SCND PHONE TCH TNE

3=CENTRAL STATION

ON BOARD DACT

1=SERVICE TERMINAL

2=SUPERV PHONE LINE

Onboard DACT Screen 1

Onboard DACT Screen 2

PHONE LINE

1=TOUCHTONE

2=ROTARY 67/33 (EURO)

3=ROTARY 60/40 (U.S.)

Primary Phone Type Screen