105

Read Status

Operating Instructions

Open Condition

IDCs and all main circuit board NACs are monitored for fault conditions during Walktest mode.
When an open condition occurs on an IDC, the FACP will activate all enabled NACs during an
audible Walktest and remain activated until the open condition is cleared.

While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of
the Program and status change operations). The alarm relay is not activated.

4.19 Read Status

Read Status functions do not require a password. The control panel will continue to provide fire
protection while in Read Status mode. This mode can be entered while the control panel is in alarm
or trouble. If a new alarm or trouble occurs during these functions, the Read Status is exited to pre-
vent confusion.

Read Status Entry

When the operator presses the control panel Enter key, the LCD will display the following:

Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Sta-
tus mode which allows the user to view and print the programmed features and status of the control
panel.

The following screens will be displayed:

4.19.1 Input Zones

Pressing 1 while viewing Read Status Screen #1 will cause the following screens to be displayed:

Pressing the down arrow key will allow the selection of Zones 4-5 for the MS-5UD and Zones 4-10
for the MS-10UD.

NOTE: In Walktest, a NAC open or short fault will not cause the NACs to activate.

1=READ STATUS MODE

2=PROGRAMMING MODE

3=FUTURE USE

4=REMOTE DOWNLOAD

READ STATUS

1=INPUT ZONES

2=NACS

3=RELAYS

READ STATUS

1=SYSTEM SETTINGS

2=TIMERS

3=DAYLIGHT SAVINGS

Read Status Screen #1

Read Status Screen #3

READ STATUS

1=HISTORY

2=PRINTER

3=ANN-BUS

Read Status Screen #2

READ STATUS

1=CENTRAL STATION

2=PHONE LINES

3=SERVICE TERMINAL

Read Status Screen #4

READ STATUS

1=INPUT ZONES

2=NACS

3=RELAYS

Read Status Screen #1

INPUT ZONES

1=ZONE 1

2=ZONE 2

3=ZONE 3