Appendix e: default programming – Fire-Lite MS-10UD Series FACP User Manual

Page 134

Advertising
background image

134

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Appendix E: Default Programming

The following table provides a list of the programming options and their factory default settings.

Program Option

Factory Default

Program Option

Factory Default

Zone #1-10 Enabled

Yes

ANN-80 Lock Enabled

Yes

Zone #1-10 Type

Pull Station

ANN-80 Acknowledge Button Enabled

Yes

Zone #1-10 PAS Pre-Signal Enabled

No Delay

ANN-80 Silence Button Enabled

Yes

Zone #1-10 Verify Enabled

No

ANN-80 Reset Button Enabled

Yes

Zone #1-10 ACC Message

No Message Active

ANN-80 Drill Button Enabled

Yes

Zone #1-10 Freeze Enabled

Yes

ACC All-Call Zone

None

Adjective

None

ANN-BUS Device 1

None

Noun

None

ANN-BUS Device 2

None

NAC #1-4 Enabled

Yes

ANN-BUS Device 3

None

NAC #1-4 Coding

Steady

ANN-BUS Device 4

None

NAC #1-4 Auto Silence

No

ANN-BUS Device 5

None

NAC #1-4 Silence Inhibit

No

ANN-BUS Device 6

None

NAC #1-4 Silenceable

Silenceable

ANN-BUS Device 7

None

Banner

ANN-BUS Device 8

None

Relay 1

Alarm

ANN-BUS Relay 1 type

Zone 1

Relay 2

Trouble

ANN-BUS Relay 2 type

Zone 2

Relay 3

Supervisory

ANN-BUS Relay 3 type

Zone 3

Trouble Reminder

No

ANN-BUS Relay 4 type

Zone 4

Canadian Option

No

ANN-BUS Relay 5 type

Zone 5

Charger Disable

No

ANN-BUS Relay 6 type

Zone 6

Factory Banner

Factory Banner

ANN-BUS Relay 7 type

Zone 7

PAS Timer

120

ANN-BUS Relay 8 type

Zone 8

Pre-Signal Timer

120

ANN-BUS Relay 9 type

Zone 9

AC Loss Timer

2

ANN-BUS Relay 10 type

Zone 10

Waterflow Delay Timer

0

Phone Line 2 Supervision

Yes

Time Format

12 Hour

Primary Phone Type

Touchtone

Daylight Savings Enabled

Yes

Secondary Phone Type

Touchtone

Daylight Savings Start Week

Week 2

Central Station Reporting Enabled

No

Daylight Savings Start Month

March

Central Station Report Type

First Available

Daylight Savings End Week

Week 1

Central Station Call Limit

0

Daylight Savings End Month

November

Central Station Primary Test Time Interval

24 Hr

Printer Port Type

Parallel Port

Central Station Primary Communication Format

Ademco Contact ID

Printer Supervision

No

Central Station Primary Phone Number

Printer Baud Rate

N/A

Central Station Primary Test Time

1:00

Printer Parity

N/A

Central Station Primary Account Code

0000

Printer Data Bits

N/A

Central Station Secondary Test Time Interval

24 Hr

Printer Stop Bits

N/A

Central Station Secondary Communication Format

Ademco Contact ID

Printer Offline Timer

60

Central Station Secondary Phone Number

ANN-BUS Enabled

No

Central Station Secondary Test Time

2:00

ANN-LED Piezo Enabled

Yes

Central Station Seocndary Account Code

0000

ANN-80 Piezo Enabled

Yes

Service Terminal Ring Count

0