2 history, 3 walktest, History 3.6.3: walktest – Fire-Lite MS-10UD Series FACP User Manual

Page 94

Advertising
background image

94

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Programming

Maintenance Programming Level

Pressing the down arrow key will display additional Zones (Zones 4 - 5 for MS-5UD and Zones 4 -
10 for MS-10UD). Select the number corresponding to the desired zone. A screen will appear
which will allow enabling or disabling of the selected zone, as illustrated in the following example:

Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No.

3.6.2 History

Pressing 2 while viewing Maintenance Screen #1 will cause the following screen to be displayed:

The History feature allows the operator to view control panel events which have been stored in a
history file in memory and erase the contents of the history file

Pressing 1 while viewing the History screen will cause the following screen to be displayed:

To view all the events which have occurred in the control panel since the history file was last
erased, press 1 while viewing the Events screen. To view only alarms/active events which have
occurred, press 2 while viewing the Events screen. To view events other than alarms, press 3. The
most recent event will be displayed on the screen. To view all of the selected events, press the up or
down arrow keys to scroll through the list of events. If no events have occurred, the display will
read NO EVENTS IN HISTORY.

Pressing 2 while viewing the History Screen will cause the following screen to be displayed:

Pressing 1 while viewing the Erase History Screen will erase all events from the History file. The
display will then return to the History Screen. Pressing 2 will cause the display to return to the His-
tory Screen without erasing the History file.

3.6.3 Walktest

To perform a walktest, press 3 while viewing Maintenance Screen #1. The following screen will be
displayed:

The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The dis-
play will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.

ZONE 1

1=ENABLED YES

Enable/Disable Select Screen

HISTORY

1=VIEW EVENTS

2=ERASE HISTORY

History Screen

HISTORY

1=VIEW ALL

2=VIEW ALARMS

3=VIEW OTHER EVENTS

ERASE HISTORY

PROCEED?

1=YES 2=NO

Erase History Screen

PROGRAMMING

1=INPUT ZONES

2=HISTORY

3=WALKTEST

Maintenance Screen #1

WALKTEST

1=SILENT

2=AUDIBLE

3=VIEW RESULT

Walktest Screen

Advertising