MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Power Supply Calculations

Calculating the System Current Draw

Table 7.3 contains three columns for calculating current draws. For maximum output current avail-
ability per circuit and per panel, refer to Section 1.2, “Specifications”, on page 15. For each col-
umn, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy
the totals from Calculation Column 2 and Calculation Column 3 to Table 7.4 on page 119.

Device Type

Calculation Column 1

Primary, Non-Fire Alarm Current

(amps)

Calculation Column 2

Secondary, Fire Alarm Current

(amps)

Calculation Column 3

Secondary, Non-Fire Alarm

Current

(amps)

Qty

X[current

draw]=

Total

Qty

X [current draw]

=

Total

Qty

X[current

draw]=

Total

Main Circuit

Board

MS-5UD

or

MS-10UD

1

X[0.110]=

X[0.133]=

1

X[0.214]

1, 2

=

X[0.282]

1, 2

=

1

X[0.110]=

X[0.133]=

CAC-5X

[ ]

X[0.001]=

[ ]

X[0.001]=

[ ]

X[0.001]=

4XTMF

[ ]

1 max.

X[0.005]=

[ ]

1 max.

X[0.011]

1

=

[ ]

1 max.

X[0.005]=

ANN-SEC card

[ ]

1 max.

X[0.003]=

[ ]

1 max.

X[0.003]=

[ ]

1 max.

X[0.003]=

ANN-80(C)

[ ]

X[0.037]=

[ ]

X[0.040]=

[ ]

X[0.015]=

ANN-I/O

[ ]

X[0.035]=

[ ]

X[0.200]=

[ ]

X[0.035]=

ANN-RLY

[ ]

X[0.015]=

[ ]

X[0.075]=

[ ]

X[0.015]=

ANN-(R)LED

3

[ ]

X[0.028]=

[ ]

X[0.068]=

[ ]

X[0.028]=

ANN-S/PG

[ ]

X[0.045]=

[ ]

X[0.045]=

[ ]

X[0.045]=

2-wire Detector

Heads

[ ]

X[ ]

4

=

[ ]

5

X[0.040]=

[ ]

X[ ]

4

=

4-wire Detector

Heads

[ ]

X[ ]

4

=

[ ]

5

X[0.040]=

[ ]

X[ ]

4

=

Power

Supervision

Relays

6

[ ]

X[0.025]=

[ ]

X[0.025]=

[ ]

X[0.025]=

NAC #1

[ ]

X[ ]=

NAC #2

[ ]

X[ ]=

NAC #3

NAC #4

Current Draw

from TB9

(nonalarm)

[ ]=

[ ]=

[ ]=

Sum each

column

7

for

totals

Primary Non-Alarm =

Secondary Alarm =

Secondary Non-Alarm =

Table 7.3 System Current Draw Calculations

1 If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add

another 0.005 amps.

2 The current draw shown represents one zone (IDC) on the main circuit board in alarm. One zone consumes

0.040 amps.

3 An ANN-LED is supplied standard with the MS-5UDC and MS-10UDC.
4 Refer to the Device Compatibility Document for standby current.
5 Enter the number of IDCs used minus one.
6 Must use compatible listed Power Supervision Relay.
7 Total current draw listed above cannot exceed 3.25 amps for the MS-5UD-3(E), 3.28 for the MS-10UD-3(E),

7.25 for the MS-5UD-7(C/E), and 7.28 for the MS-10UD-7(C/E).