4 output circuits, 1 notification appliance circuits, Output circuits – Fire-Lite MS-10UD Series FACP User Manual

Page 32: Notification appliance circuits

Advertising
background image

32

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Installation

Output Circuits

2.4 Output Circuits

2.4.1 Notification Appliance Circuits

Total current drawn from the four Style Y (Class B) Notification Appliance Circuits as well as other
DC power outputs cannot exceed 3.0 amps for the MS-5UD-3(E), MS-10UD-3(E) [2.5 amp maxi-
mum per NAC] powered by the FLPS-3 power supply or 7.0 amps for the MS-5UD-7(C/E), MS-
10UD-7(C/E) [3.0 amps maximum per NAC] powered by the FLPS-7 power supply (refer to
“Power Supply Calculations” on page 116). Each circuit is supervised, power-limited and provides
special application power. Refer to the Fire•Lite Device Compatibility Document for a listing of
compatible notification appliances.

The NACs can be converted to Style Z (Class A) by installing the optional Class A Converter mod-
ule. Refer to “CAC-5X Class A Converter Module” on page 37.

For FCC compliance with Class B wiring, a ferrite bead (supplied) is required for NAC 1 and for
NAC 2. If using both NAC 1 and NAC 2 with Class B wiring, a single ferrite may be used with
wiring as shown in Figure 2.7.

Figure 2.7 NAC Connections

Class B Notification Appliance Circuits (supervised and power-limited)

4.7 K

, ½ watt resistor P/N:71252

Dummy load any unused circuits (P/N: 71245)

Polarized Bell

Polarized Strobe

Polarized Horn

Polarized Horn

Polarized Horn-Strobe

Polarized Bell

Notification Appliance Circuit
polarity shown in alarm condition

ms-1

0UD

na

c.w

mf

+ - + -

Ferrite Bead

p/n 50116546-001

Advertising