Master Programming Level

Programming

Trouble Call Limit (Dialer Runaway Prevention)

The Call Limit option limits the number of DACT trouble calls to the Central Station, to a pro-
grammed amount between 0 and 99, for each unique trouble within a 24 hour period. All call limit
counters reset (clear) at each midnight. Separate limit counters keep track of each unique type of
trouble. Note that the number of phone line (communication) faults called to the Central Station
are not limited by this feature. No subsequent restoral message is sent to the Central Station(s) for
a particular trouble whose call limit has been reached. Local DACT annunciation will still track the
particular trouble and restoral.

To set the Trouble Call Limit, press 3 while viewing Central Station Screen #2. The following
screen will be displayed.

Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.

Service Terminal

The FACP can be programmed remotely from a PC using a modem and telephone line. Informa-
tion can also be retrieved from the FACP using the same method. The Upload/Download option
allows an operator to set the necessary parameters to allow the uploading and downloading of data
between the FACP and PC. The Service Terminal selection provides the means for entering these
parameters.

Pressing 1 while viewing Onboard DACT Screen #2 will cause the following screens to appear:

Ring Count

The ring count designates the number of rings allowed on the phone line prior to answering an
incoming call from a service terminal. The factory default is 0 which means the control panel will
not answer an incoming call. This entry may be programmed for 1 to 25 rings.

Secondary # System Off Normal

LB

LX

Secondary # System Test Message

RP

000

Secondary # System Abnormal Test Message

RP99

000

Secondary # Power Supply Sync Fault

OU

OV

Secondary # Upload/Download Request

RB

000

Secondary # Upload Successful

RS

000

Secondary # Download Successful

RS

000

Secondary # Upload/Download Failed

RU

000

Secondary # Voice EVAC Fault

ET

ER

Secondary # Power Supply Sync Fault

OU

OV

Table 3.7 SIA-DCS Secondary # Event Codes (Continued)

CENTRAL STATION

1=PRIMARY

2=SECONDARY

3=CALL LIMIT

Central Station Screen #2

TROUBLE CALL LIMIT

RANGE 00-99 TROUBLES

Backup Reporting Screen

NOTE: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the
Central Station an unlimited amount of times. This is the factory default setting.

DACT

1=SERVICE TERMINAL

2=SUPERV PHONE LINE

Onboard DACT Screen #2

SERVICE TERMINAL

1=RING COUNT 0

Service Terminal Screen

SERVICE TERMINAL

1=RING COUNT

Service Terminal Screen #2