12 visualisation with »visiwinnet – Lenze c300 User Manual

Page 121

Advertising
background image

12

Visualisation with »VisiWinNET®«

12.7

OPC tunnel for external visualisation (remote access)

121

Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.7.1.1

Configure OPC tunnel for remote access (Windows® CE)

For the configuration of the OPC tunnel, the oct.xml configuration file must be edited.
In our example, the IP address of the Controller controller is: 192.168.5.99

• For configuring OPC tunnel 1, use the oct.xml configuration file in the \USBStorage\OCT

storage\OCT directory. Enter the corresponding IP address of the control controller in the

configuration file (as described in the following section).

• For configuring OPC tunnel 2, standard settings need not be changed (configuration file:

oct.xml).

Preparation
Read in the SD card of the visualisation Controller on your PC using a card reader.
or
Establish an FTP connection between your PC and the visualisation Controller.

FTP settings with the »WebConfig«

( 86)

How to set up an external visualisation on the controller:

1. Go to the \USBStorage\OCT directory.
2. Rename the oct.xml file to oct_save.xml
3. Rename the octvisu.xml file to oct.xml
4. Open the oct.xml file using an editor.

This is a text file. Use the Software Microsoft Editor, for instance, for edition.

5. Go to the following section:

6. Enter the IP address of the controller (with the control function).
7. Line contents (example):

8. Save changed file on the SD card.
9. Restart the controller (with the visualisation function).

The OPC servers of the control controller can now be accessed.

Tip!
To undo faulty changes in the configuration files, the original state of the configuration

files can be restored. For this, delete all configuration files from the \USBStorage\OCT

directory and restart the controller.

<Server ID="RemoteIPC" URL="tpda://172.31.207.56:56765" ProvideItems="dynamic"
ItemPre-fix="RemoteIPC" EstablishConnection="on demand"/>

<Server ID="RemoteIPC" URL="tpda://

192.168.5.99:56765" ProvideItems="dynamic" ItemPre-

fix="RemoteIPC" EstablishConnection="on demand"/>