13 parameter reference – Lenze c300 User Manual

Page 160

Advertising
background image

Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17

160

13

Parameter reference

13.3

Voltage buffering by external UPS (optional, for Controller 3241 C)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C0212

C0213

C0214

Parameter | Name:

C0212 | UPS: Firmware version

Data type: VISIBLE_STRING

Index: 24363

d

= 5F2B

h

Version of the UPS firmware

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0213 | UPS: Buffer time without action

Data type: UNSIGNED_16

Index: 24362

d

= 5F2A

h

The UPS buffers the system without any further action. If the voltage dip lasts longer than the time set here:

• The PLC is stopped.

• The PLC saves the retain variables, logbook entries and visualisation data (trends and alarms).

• The timer

C00214

is started.

Selection list

(Lenze setting printed in bold)

Info

0 0

250 250
500 500
750 750

1000 1000
1250 1250
1500 1500
1750 1750
2000 2000
2250 2250
2500 2500
2750 2750
3000 3000
3250 3250
3500 3500
3750 3750
4000 4000
4250 4250
4500 4500
4750 4750
5000 5000

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0214 | UPS: Buffer time until shutdown

Data type: UNSIGNED_8

Index: 24361

d

= 5F29

h

After expiration of the time set here, the system is shut down. If the voltage is applied once again, the system is

restarted automatically.
Setting range

(min. value | unit | max. value)

Lenze setting

0

s

255 10 s

Read access  Write access  CINH  PLC-STOP  No transfer