Device replacement - replacing the controller (in the event of

service)

77

Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.4

Subsequent use of retain data on the new controller

How to proceed in case of 3221 C/3231 C:
In order to be able to further use the retain data of the Controllers 3221 C/3231 C after a

device replacement, ...

• save the desired data to the SD card from the application;
• restore the desired data from the application.

Further information on the use of retain variables.

Creating remanent variables (retain/persistent)

( 64)

Storage of retain data on the SD card (only Controllers 3221 C/3231 C)

( 65)

Note!

Depending on the used controller, the retain data of the PLC may no longer be available

after a voltage failure/device replacement.

Controllers 3221 C/3231 C save the retain data internally (in the device, not on the SD

card). Hence, the retain data of the replacement device correspond to the output

values (default values).

• The Controllers 3241 C, c300, p300 and p500 save the retain data on the SD card.