Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17

164

13

Parameter reference

13.5

EtherCAT

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C281/5

C281/6

C282/2

Parameter | Name:

C281/5 | ECAT master: State information

Data type: UNSIGNED_32

Index: 24294.5

d

=

0x5EE6.0x05

h

Display of additional information on the current state of the master

The bits are set to value 1 if the respective states are reached.
Value is bit-coded:

Bit 0 Master ok
Bit 1 Reserved 1
Bit 2 Reserved 2
Bit 3 Reserved 3
Bit 4 Init
Bit 5 Pre-operational
Bit 6 Safe-operational
Bit 7 Operational
Bit 8 Slaves in requested state
Bit 9 Master in requested state

Bit 10 Bus Scan Match
Bit 11 Reserved 4
Bit 12 DC: Activated
Bit 13 DC: Synchronised
Bit 14 DC: Busy
Bit 15 Reserved 5
Bit 16 Link Up
Bit 17 Reserved 6

... ...

Bit 31 Reserved 20

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C281/6 | ECAT bus scan

Data type: UNSIGNED_8

Index: 24294.6

d

=

0x5EE6.0x06

h

Activation of the fieldbus scan

The fieldbus scan updates all EtherCAT codes.
Selection list

(Lenze setting printed in bold)

0 No Operation
1 The bus is scanned

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C282/2 | ECAT DC: Perm. dev. slave sync

Data type: UNSIGNED_32

Index: 24293.2

d

=

0x5EE5.0x02

h

Permissible deviation of the distributed clocks of all devices in nanoseconds. If the permissible deviation is

exceeded, the master will initiate a resynchronisation of the distributed clocks.
Display range

(min. value | unit | max. value)

0

ns

4294967295

Read access  Write access  CINH  PLC-STOP  No transfer