13 parameter reference – Lenze c300 User Manual

Page 148

Advertising
background image

Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17

148

13

Parameter reference

13.2

Basic parameters of the Controllers 3200 C/c300 and p300/p500

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C0120

C0122

C0123

C0124

C0125

C0126

Parameter | Name:

C0120 | WinCE user: User 3 with telnet permissions

Data type: UNSIGNED_8

Index: 24455

d

= 5F87

h

User may use telnet
Setting range

(min. value | unit | max. value)

Lenze setting

0

1 0

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0122 | WinCe users: User name 4

Data type: VISIBLE_STRING

Index: 24453

d

= 5F85

h

Name of the user

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0123 | WinCe users: Password 4

Data type: VISIBLE_STRING

Index: 24452

d

= 5F84

h

Password of the user

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0124 | WinCE users: User 4 with FTP permissions

Data type: UNSIGNED_8

Index: 24451

d

= 5F83

h

User may use FTP
Setting range

(min. value | unit | max. value)

Lenze setting

0

1 0

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0125 | FTP: Permissions user 4

Data type: UNSIGNED_32

Index: 24450

d

= 5F82

h

FTP rights of the user.
Value is bit-coded:

Bit 0 Allow Read
Bit 1 Allow Write
Bit 2 Virtual Roots
Bit 3 Allow Hidden Files

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0126 | FTP: Home user 4

Data type: VISIBLE_STRING

Index: 24449

d

= 5F81

h

Home directory of the user

Read access  Write access  CINH  PLC-STOP  No transfer