Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17

70

9

Data integrity in the event of a voltage failure

9.2

Storage of »VisiWinNET® Smart« visualisation data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2

Storage of »VisiWinNET® Smart« visualisation data

The Controllers 3231 C cyclically store »VisiWinNET® Smart« visualisation data (user-specific trends,

alarms, recipes) every 60 seconds.

In the event of a voltage failure, the Controllers 3241 C store the »VisiWinNET® Smart« visualisation

data (user-specific trends, alarms, recipes) exactly isochronously to the SD card.
In the event of a voltage failure, the Controllers c300/p300/p500 store the »VisiWinNET® Smart«

visualisation data (user-specific trends, alarms, recipes) exactly isochronously to the memory card.

This is made possible by the high-capacity, integrated UPS.

Note!

Controller 3231 C:
Depending on the time of occurrence of the voltage failure, the data saved last may be

out-of-date by up to one minute.
There is a time period of one minute between two storage processes. Hence, the saved

visualisation data is not exactly up-to-date after a voltage failure.