Voltage, 13 parameter reference – Lenze c300 User Manual

Page 158

Advertising
background image

Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17

158

13

Parameter reference

13.3

Voltage buffering by external UPS (optional, for Controller 3241 C)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

13.3

Voltage buffering by external UPS (optional, for Controller 3241 C)

This chapter lists all UPS parameters in numerically ascending order.

UPS functionality of the controllers

( 68)

C0203

C0204

C0205

Parameter | Name:

C0203 | UPS: UPS monitoring

Data type: UNSIGNED_8

Index: 24372

d

= 5F34

h

Enable monitoring via an external UPS (optional)
Selection list

(Lenze setting printed in bold)

Info

0 Off
1 On

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0204 | UPS: Status

Data type: UNSIGNED_8

Index: 24371

d

= 5F33

h

Status of the external UPS
Selection list

(read only)

Info

0 ACU Controller is missing

85 Battery / capacitor is loaded
86 Battery / capacitor is being loaded
87 -
88 -
89 UPS is buffering the system
90 Battery / capacitor short circuit
91 Battery / capacitor is missing
92 Battery / capacitor is defective
93 ACU Controller is defective
94 -
95 Undefined status of battery /

capacitor

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0205 | UPS: Supply voltage

Data type: FLOAT_32

Index: 24370

d

= 5F32

h

Supply voltage of the external UPS in [V]
Display range

(min. value | unit | max. value)

0

V

34

Read access  Write access  CINH  PLC-STOP  No transfer