Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 103

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

Troubleshooting 7-7

I/O Module Configuration Mismatch Fault Codes - Code 3

Addressing Mode mismatch.
1/2-slot, 1-slot, and 2-slot indicates previously
saved selection.

Specialty I/O Mode mismatch.
Discrete (dSc) or Block Transfer (bL) indicates
previously saved selection.

(1)

C stands for configuration, the first number from the left is the DIP switch number (SW1,
SW2, or SW3). The second number stands for the highest individual switch number (1 - 8).
C38 is switch SW3, switch 8.

(2)

This is the saved parameter setting.

or

or

or

Code 3

(1)

Meaning

I/O module missing from the previously saved configuration.

I/O module detected in an unused slot of the previously saved
configuration.

I/O Module Electrical Interface Type. Not the same as the saved
configuration such as a DC output module being placed in an AC
output slot.

I/O Module Mix or Class. Not the same as the saved
configuration such as a DC 16-point input module placed in an 8
point DC input slot.

(1) The fault code is alternated with the corresponding slot number (L slot#).