Slot numbering, Addressing i/o modules, Slot numbering -2 addressing i/o modules -2 – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 38

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

3-2 Addressing

Slot Numbering

The 1747-ASB module is capable of controlling 30 slots. When
expansion chassis are used, the 1747-ASB module treats all of the I/O
modules as if they are installed in a single chassis.

The remote chassis and remote expansion chassis slots are numbered
from 0 to 30. The 1747-ASB module must reside in slot 0. Slots
numbered 31 and above cannot be used.

Addressing I/O Modules

SLC and PLC processors address the I/O modules residing in the
1747-ASB module chassis by logical rack and logical group. Before
using the 1747-ASB module, you should first understand slot
addressing and how each module's image is mapped into the
1747-ASB module's image.

IMPORTANT

A 1747-ASB module fault occurs if the remote
expansion chassis are not powered.

Catalog Number 1746-C9

Catalog Number 1746-C7

Remote Chassis

Remote Chassis

Remote Expansion Chassis

Catalog Number 1746-P1

Catalog Number 1746-P3

Catalog Number 1746-P2

Catalog Number 1746-P2

36 inch cable

6 inch
cable

Remote Expansion Chassis

IMPORTANT

Installing modules in slots 31 and above causes a
1747-ASB module error.