Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 139

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

Specifications A-11

1. T

dm-nbt

equals 80ms

(1)

for a specific pair of discretely mapped

input and output modules. The maximum throughput for these
discretely mapped I/O modules when block transfers are
present are:

T

dm-bt

= T

dm-nbt

+ 2T

btx

T

dm-bt

= 80ms + 2T

btx

2. Determine the maximum length of the block transfer to each

logical device. There are two logical devices for the 1747-ASB
module. The largest block transfer that is possible with the full
logical rack, logical device is 8 words. The largest block
transfer that is possible with the 1/2 logical rack, logical device
is 2 words.

3. Substitute the maximum length of each logical device into:

T

ri

= 0.150 x block transfer length + 3.5ms

T

ri

= (0.150 x 8 ) + 3.5ms

T

ri1

= 4.7ms

T

ri

= (0.150 x 2 ) + 3.5ms

T

ri2

= 3.8ms

4. There is one logical device for each 1771-ASB module. The

largest block transfer for 1/4 logical racks is 64 words. Calculate
the maximum length for these logical devices:

T

ri

= 0.150 x block transfer length + 3.5ms

T

ri

= (0.150 x 64 ) + 3.5ms

T

ri3 & 4

= 13.1ms

5. Add up all of the maximum word lengths:

T

btx

= T

ri1

+T

ri2

+

T

ri3

+

T

ri

4

T

btx

= 4.7+ 3.8

+

13.1 +

13.1

T

btx

= 34.7ms

(1) This number is arbitrarily assigned.