Application Examples 8-7

Application Example Program

Shown below is an excerpt from the user program. When the switch is
closed, bulbs 1 and 2 turn on and the decimal value 5555 is moved to
analog output 1 and is converted to an analog signal.

This application consists of an SLC 5/02 processor controlling local

and remote I/O.

(1)

The local I/O resides in a 4-slot chassis, consisting

of:

1746-OW8, 8-point AC/DC relay output module

1746-IA8, 8-point AC input module

Basic SLC 500 Example
Using and RIO Scanner

An RIO scanner, Catalog Number 1747-SN, resides in slot 3 of the local
chassis. The scanner controls two remote expansion chassis (one
7-slot and one 4-slot) and a RediPANEL.

1747-ASB module 1 controls the following I/O modules:

1746-NIO4I, analog module (2 current/voltage inputs and 2
current outputs)

1746-IV32, 32-point 24VDC sourcing input module

1746-OV32, 32-point 24VDC sinking output module

1746-OB16, 16-point DC sourcing output module

1746-OA16, 16-point AC output module

(1) An SLC 5/02 or greater processor is needed for the RIO scanner.

] [

I:3.0

15

( )

O:3.4

MOV

MOVE
Source

5555

Dest

O:2.1

4

( )

O:3.3

12

Bulb 1

Bulb 2

Switch

Meter