Sw3 -23 – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual
Page 77
Advertising
Publication 1747-UM006B-EN-P - June 2003
Configuration 4-23
SW3
•
Hold Last State
ON=Hold Last State
OFF=Do Not HOld Last State
(default)
•
Processor Restart Lockout
ON=Automatic Restart (default)
OFF=Processor Lockout
•
Link Response
ON=Restricted (default)
OFF=Unrestricted
•
Last Chassis
ON=Not Last Chassis (default)
OFF=Last Chassis
•
Addressing Mode
SW3
1
O
N
24
5
6
7
8
3
Hold Last State
Processor Restart Lockout
Link Response
Last Chassis/PLC-3 Backup
Addressing Mode Bit 1 (MSB)
Addressing Mode Bit 0 (LSB)
Specialty I/O Mode
I/O Module Keying
5
6
Address
ON
ON
Invalid
ON
OFF
1-slot Addressing
(default)
OFF
ON
1/2-slot Addressing
OFF
OFF
2-slot Addressing