Publication 1747-UM006B-EN-P - June 2003

A-10 Specifications

words sent in the block transfer and the selected baud rate. RIO link
protocol allows for a maximum of one RIO block transfer to be sent to
each logical device on the RIO link during any single RIO scan. The
RIO scan increase (T

ri

) for each logical device is:

The total increase in the RIO scan time (T

btx

) is equal to:

T

btx

= sum of T

ri

for all logical devices

Discrete I/O Throughput with Block Transfers Present Example

A PLC 5/40 is controlling a 115.2K baud RIO link that has 3 adapters
and 4 logical devices.

1747-ASB module:

starting logical rack 0, logical group 0

12 logical groups (1 1/2 logical racks)

one 8 word and two 4 word block transfer write/read modules
in logical rack 0

one 2 word block transfer write/read module in logical rack 1

1771-ASB module:

starting logical rack 2, logical group 0

2 logical groups (1/4 logical racks)

one 64 word block transfer write/read module

1771-ASB module

starting logical rack 2, logical group 2

2 logical groups (1/4 logical racks)

one 64 word block transfer write/read module

Baud Rate

RIO Scan Time Increase (T

ri

)

57.6K baud

0.300 x block transfer length + 5.0ms

115.2K baud

0.150 x block transfer length + 3.5ms

230.4K baud

0.075 x block transfer length + 2.0ms