Publication 1747-UM006B-EN-P - June 2003

Application Examples 8-19

1747-ASB Module 1 Configuration Details

Because the image of the 1747-ASB module 1 crosses logical rack
boundary 1 and 2, 1747-ASB module 1 appears as two logical devices
to the RIO scanner.

1747-ASB module 1 is configured for last chassis because it has the
highest numbered logical group (group 5) in its highest numbered
logical rack (logical rack 2).

1747-ASB module 1 is configured for hold last state and processor
restart lockout. If the RIO communications cable is removed and
reconnected during normal RIO communications, the discrete outputs
remain in their last state and the 1747-ASB module does not resume
communicating with the scanner until the processor restart lockout
terminals are momentarily shorted together. For more information
regarding processor restart lockout, refer to chapter 4.

1747-ASB module 1 is configured as a complementary chassis.
Because complementary I/O is not being used, there is no need for a
primary chassis.

The 1747-ASB module 1 response time is unrestricted because the
PLC-5/40 does not require a restricted response time.

Bit Number

Octal

Logical

Rack 1

0

7

10

17

Logical

Rack 2

PLC Processor Input Image

Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7

1747-ASB
Module 1

NIO4V

IA16

IA16
IG16

IG16

Bit Number

Octal

Logical

Rack 1

0

7

10

17

Logical

Rack 2

PLC Processor Output Image

Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7

Not Used
Not Used
Not Used
Not Used
Not Used
Not Used

IB16

IB16

NO4V

IA16

IA16

IV16

IV16

Not Used
Not Used

1747-ASB
Module 1

NIO4V

OW16

OW16

OG16

OG16

Not Used
Not Used
Not Used
Not Used
Not Used
Not Used

OB16

OB16

NO4V

OW16

OW16

OV16

OV16

Not Used
Not Used

OW8

OV8

OW8

OA8

I:010
I:01 1
I:012
I:013
I:014
I:015
I:016
I:017
I:020
I:021
I:022
I:023
I:024
I:025
I:026
I:027

O:010
O:01 1
O:012
O:013
O:014
O:015
O:016
O:017
O:020
O:021
O:022
O:023
O:024
O:025
O:026
O:027

IMPORTANT

Selecting processor restart lockout disables PLC auto
configurations on the 1747-ASB module except for
initial powerup. If processor restart lockout is not
selected, you are able to perform PLC auto
configurations on the 1747-ASB module.