Publication 1747-UM006B-EN-P - June 2003

6-4 Start-Up and Operation

Inhibit Condition

When any of the 1747-ASB module's logical devices are inhibited
before communication with all of its logical devices occur at least
once:

The inhibited logical devices do not communicate on the RIO
link.

The enabled logical devices communicate on the RIO link.

The 1747-ASB module does not send output data to any of its
output modules, even those that are enabled.

The 1747-ASB module does not process any RIO block transfer
writes.

The 1747-ASB module sends new input data from its input
modules to the scanner for enabled devices.

The 1747-ASB module processes RIO block transfers reads for
enabled devices.

The position of the processor restart lockout switch (PRL) affects the
1747-ASB module's inhibit functionality. If processor restart lockout is
selected, and any logical device assigned to the 1747-ASB module is
inhibited after all of the logical devices have received RIO link
communications from the scanner at least once:

All of the 1747-ASB module's logical devices stop
communicating on the RIO link.

The 1747-ASB module does not send any output data to any of
its output modules.

Discrete outputs are held in their last state if hold last state is
selected, or discrete outputs are reset if hold last state is not
selected.

The 1747-ASB module does not process any RIO block transfers.

If processor restart lockout is not selected and any logical device
assigned to the 1747-ASB module is inhibited after all of the logical
devices have received RIO link communications from the scanner at
least once:

The inhibited logical devices stop communicating on the RIO
link.

The enabled logical devices continue to communicate on the
RIO link.

The 1747-ASB module does not send new output data to any
logical device output module, even those that are enabled.