Specialty i/o mode dip switch settings, Specialty i/o mode (sw3-7), I/o module keying (sw3-8) – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 75

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

Configuration 4-21

If the invalid switch setting is selected, a 1747-ASB module error
occurs.

1/2-slot addressing is not supported by the PLC-2 family of processors.

Specialty I/O Mode (SW3-7)

SW3 switch 7 determines the specialty I/O mode (discrete or block
transfer).

Specialty I/O Mode DIP Switch Settings

The 1747-ASB module is shipped from the factory with the default
position ON (discrete).

For an overview of discrete and block transfer modes, refer to page
3-13.

I/O Module Keying (SW3-8)

SW3 switch 8 provides I/O module keying, that prevents you from
operating the 1747-ASB module when the I/O module or DIP switch
configuration (other than the keying DIP switch itself) differs from the
last time you saved it. There are two modes, save and check.

When power is applied in save mode and the DIP switch and I/O
module configurations are valid, the 1747-ASB module saves the DIP
switch and I/O module configuration in non-volatile memory.

When power is applied in check mode, the 1747-ASB module
compares the stored DIP switch and I/O module configuration to the
current DIP switch and I/O module configuration. If the
configurations do not match, a 1747-ASB module error occurs.

SW3

Discrete

4

1

23

5

6

7

8

O

N

SW3

Block Transfer

4

1

23

5

6

7

8

O

N

4

1

23

4
5
6

7

8

SW1

S

W2

SW3

1

23

5
6

7

8

1
23

4
5
6

7

8

O

N

O

N

O

N

Specialty I/O Mode
I/O Module Keying

Addressing Mode

Last Chassis/PLC-3 Backup

Link Response

Processor Restart Lockout

Hold Last State

Baud Rate

Primary/Complementary Chassis

ASB Module Image Size

Logical Group Number

Logical Rack Number

ON

OFF

Reserved