Publication 1747-UM006B-EN-P - June 2003

Installation and Wiring 5-5

Wiring a Processor Restart
Lockout Switch

When processor restart lockout is enabled (SW3-2) and
communications are restored, the 1747-ASB module does not respond
to any type of communications, or communication commands until
terminals IN and RET are momentarily shorted together. This occurs
while the RIO scanner is attempting to communicate with the
1747-ASB module.

You must use a momentary switch (Class 1, Division 2) to short the
terminals together. The processor restart lockout is removed as soon
as the switch toggles back to the open circuit position.

A maximum of five feet of 14-24 gauge wire (solid or stranded) is
recommended to connect the switch to the terminal.

IMPORTANT

Do not connect anything to the NC (No Connect)
terminal.

ATTENTION

!

Cycling power on any 1747-ASB module chassis
removes the processor restart lockout condition by
re-initializing the 1747-ASB module.

Momentary Switch

14 – 24 gauge wire

ADAPTER

1 23

45

6

7

8

SW1

1 2

3

456

7
8

SW2

1 2

3

4

5

678

SW3

O

N

O

N

LINE 1

SHLD
LINE 2
NC
IN
RET

(MSB)

LOGICAL
RACK

(LSB)

LOGICAL

GROUP

BAUD
RATE

PRI/COMP

RSV
(MSB)

(LSB)

IMAGE
SIZE

HLS
PRL

RESP

LAST CHA

ADDR
MODE

SP MODE

KEY

1747–ASB

ST ATUS

COMM

F AUL T

LINE 1 (Blue wire)

SHLD (Shield wire)
LINE 2 (Clear wire)

NC (No Connect)

IN

RET

IMPORTANT

Do not connect anything to the NC (No Connect)
terminal.