Publication 1747-UM006B-EN-P - June 2003

Chapter

6

Start-Up and Operation

This chapter guides you through:

system start-up

powerup and initialization sequences

initial link communications

normal operation

communication exceptions

remote expansion chassis power loss

invalid RIO link transfers

testing the 1747-ASB module

Make sure SW3-8 is ON (save mode) while you setup and debug your
system. When you have completed debugging your system:

System Start-Up

1. Cycle the power one last time in save mode (SW3-8 ON).

2. Remove power from the system.

3. Remove the 1747-ASB module and set SW3-8 to the OFF

position (check mode).

4. Replace the 1747-ASB module in slot 0.

5. Apply power to your system.

Any future changes to the 1747-ASB module's DIP switch or I/O
module configuration results in a 1747-ASB module error, as long as
the 1747-ASB module is in check mode.

The powerup and initialization sequence depends on whether the
1747-ASB module is in the save or check mode (SW3-8). RIO
communications do not commence until a powerup and initialization
sequence is complete.

Powerup and Initialization
Sequences

Power must be applied to all of the remote chassis and remote
expansion chassis controlled by the 1747-ASB module before this
sequence can be completed. If the remote expansion chassis are not
powered, a 1747-ASB module error occurs.