I/o module keying dip switch settings, Switch setting summary, Switch setting summary -22 – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 76: Sw2 -22

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

4-22 Configuration

I/O Module Keying DIP Switch Settings

The 1747-ASB module is shipped from the factory with the default
position ON (save mode).

Switch Setting Summary

The following is a summary listing the various DIP switch settings.

IMPORTANT

Use save mode during setup and debug. After
debugging is complete, power up in save mode one
last time. Remove power and place the 1747-ASB
module in check mode prior to normal operation.

SW3

Save Mode

4

1

23

5

6

7

8

O

N

SW3

Check Mode

4

1

23

5

6

7

8

O

N

SW1

Logical Rack Number
For details, see page 4-2.

Logical Group Number

SW2

Baud Rate

Primary/Complementary Chassis
ON=Primary
OFF=Complementary (default)

1747-ASB Module Image Size
For details, see page 4-9.

1

O

N

24

5
6

7
8

3

SW1

Logical Rack Number Bit 5 (MSB)

Logical Rack Number Bit 4
Logical Rack Number Bit 3

Logical Rack Number Bit 2
Logical Rack Number Bit 1
Logical Rack Number Bit 0 (LSB)
Logical Group Number Bit 1 (MSB)
Logical Group Number Bit 0 (LSB)

7

8

Group

ON

ON

0 (default)

ON

OFF

2

OFF

ON

4

OFF

OFF

6

SW2

1

O

N

24

5
6

7
8

3

Baud Rate Bit 1 (MSB)
Baud Rate Bit 0 (LSB)
Primary/Complementary Chassis

Reserved
ASB Module Image Size Bit 3 (MSB)
ASB Module Image Size Bit 2
ASB Module Image Size Bit 1
ASB Module Image Size Bit 0 (LSB)