A-4 Specifications

Calculating Throughput

The 1747-ASB module throughput is determined by more than the
1747-ASB module itself. The input and output module delays, scanner
scan time, and processor scan time contribute to throughput as well.

Discrete I/O Throughput without Block Transfers Present

The information in this section is used to calculate the discrete
throughput of the 1747-ASB module if both conditions are true:

There are no block transfer mapped I/O modules in the
1747-ASB chassis.

There are no RIO block transfers occurring on the RIO link to
any chassis.

If RIO block transfers are present on the RIO link or if the 1747-ASB
chassis has block transfer mapped I/O modules, you must use the
Discrete I/O Throughput with Block Transfers Present section.

The formula to calculate the maximum 1747-ASB module discrete I/O
throughput without block transfers present is:

T

dm-nbt

= 2T

ps

+ 2T

RIO

+ 2T

bp

+ T

SNo

+ T

SNi

+ T

id

+ T

od

+ 10ms

(1)

T

dm-nbt

= The maximum 1747-ASB module discrete throughput

without block transfers in milliseconds (ms)

To calculate throughput, substitute values for the variables in the
formula above. Locate these values in the following documents:

(1) The value of 10ms is for PLC-5/11, -5/20, -5/30, -5/40, and -5/60 processors only. For all other processors the

value is not used.

Variable

Variable Description

Location of Variable

T

ps

The total processor scan time (ms)

PLC or SLC programming manual

T

SNi

The scanner module input delay time (ms)
(only if scanner is a separate module,
otherwise value is 0)

scanner user manual

T

SNo

The scanner module output delay time (ms)
(only if scanner is a separate module,
otherwise value is 0)

scanner user manual

T

id

The input delay time (ms)

SLC I/O technical data and I/O
instruction sheets

T

od

The output delay time (ms)

SLC I/O technical data and I/O
installation instructions

T

RIO

The total RIO scan time (ms)

page A-5 of this manual

T

bp

1747-ASB module backplane scan time (ms)

page A-6 of this manual

Advertising