Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 136

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

A-8 Specifications

These values are listed in the Backplane Scan Time table on page A-6.

4. Add the backplane scan times together for each module in slots

one, two, and three.

T

base backplane scan time

(T

b

) = T

I/O module 1

+ T

I/O module 2

+

T

I/O module 3

T

b

= 0.325ms + 0.273ms + 0.625ms + 0.620ms

T

b

= 1.843ms

5. Use the appropriate Total Backplane Scan Time formula found

on page A-6 to calculate the total backplane scan time.

T

bp

= 1.32T

b

+ 1.58

T

bp

= 1.32(1.843ms) + 1.58

T

bp

= 4.01ms

6. Calculate the total RIO scan time (T

RIO

). Locate the baud rate

(115.2K) and adapter size which is found in the table on page
A-5. Multiply the RIO scan times listed under the 115.2K
heading by the number of each different type of rack that you
have. Add those numbers together:

T

RIO

= T

adapter 1

+ T

adapter 2

+ T

adapter 3

T

RIO

= 1(4.0ms) + 2(5.0ms) + 3(3.5ms)

T

RIO

= 24.5ms

7. Substitute all the values for variables in the throughput formula

and solve for throughput:

T

dm-nbt

= 2T

ps

+ 2T

RIO

+ 2T

bp

+ T

SNo

+ T

SNi

+ T

id

+ T

od

+ 10ms

(1)

T

dm-nbt

= 2(25)+ 2(24.5) + 2(4.01) + 0 + 0 + 10.0 + 1.0 + 10

T

dm-nbt

= 128.02 ms = maximum throughput

(1) The value of 10 ms is for PLC-5/11, -5/20, -5/30, -5/40, and -5/60 processors only. For all other PLC-5

processors the value is not required.