Rio device configuration -17, Rio device configuration – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 121

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

Application Examples 8-17

RIO Device Configuration

The 1747-ASB modules are configured in the following manner.

The 1771 chassis is configured for 1-slot addressing. The PLC-5/40 is
configured for scanner mode operation at 57.6K baud.

ASB 1

1746

–NIO4

V

1746

–OW8

1746

–OW16

1746

–IA16

1746

–OG16

1746

–IG16

ASB 2

1746

–NI4

1746

–NO4I

1746

–NIO4I

1746

–OW8

1746

–OV8

1746

–OB16

1746

–IB16

1746

–OA8

1746

–NO4V

1746

–OW16

1746

–IA16

1746

–OV16

1746

–IV16

The switch is connected
to input 12.

The bulb is connected
to output 5.

Meter 2 is connected
to output 2.

Meter 1 is connected
to output 0.

0

1

2

3

4

5

6

7

8

9 10

11 12 13

14 15 16

0

1

2

3

0

1

2

3

PLC-5/40

IMPORTANT

All bit numbers in this example are in octal. The
1746 16- and 32-point modules must have their LED
numbers and wiring terminal numbers labeled in
octal. All Series C or later modules include an octal
conversion kit which allows you to convert from
decimal to octal. This kit is also available as a
replacement part through your Rockwell Automation
distributor.

Function

1747-ASB Module 1

1747-ASB Module 2

Starting logical rack number

1

3

Starting logical group number

6

0

Image size (number of logical groups)

8

6

Addressing mode

2-slot

1/2-slot

Specialty I/O mode

Block transfer

(1)

Discrete

Baud rate

57.6K

57.6K

Last chassis

Yes

Yes

Hold last state

Yes

No

Processor restart lockout

Yes

No

Link response

Unrestricted

Unrestricted

Primary/complementary chassis

Complementary

Complementary

(1) When block transfer mode is selected, all specialty I/O modules are block transfer mapped. Their data is

exchanged on the RIO link using RIO block transfers.