Rio address label examples -5, Rio address label examples, Slc processor input image – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 109: Slc processor output image

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

Application Examples 8-5

Three input and output image words are not used. However, when
using 16-point I/O, 1-slot addressing provides I/O configuration
flexibility. The modules can be inserted into any slot, in any order.

Slots 1, 2, and 3 contain 16-point input modules. The output words
assigned to these slots are unused.

Slots 4, 5, and 6 contain 16-point output modules. The input words
assigned to these slots are unused.

RIO Address Label Examples

Due to the 1747-ASB module's addressing modes and RIO link
operation, the I/O modules controlled by the 1747-ASB module are
addressed by the SLC processor based on the slot location of the SN
and the word that the I/O module uses in the SN image. A label kit is
included with each 1747-ASB module to assist you in addressing I/O
modules.

Bit Number (Decimal)

0

7

8

15

Logical

Rack 0

SLC Processor Input Image

Local SLC Chassis

I:2.0 & .1
I:3.0
I:3.1
I:3.2
I:3.3
I:3.4
I:3.5
I:3.6
I:3.7

Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7

NIO4I

NIO4I

Bit Number (Decimal)

0

7

8

15

Logical

Rack 0

SLC Processor Output Image

O:2.0
O:3.0
O:3.1
O:3.2
O:3.3
O:3.4
O:3.5
O:3.6
O:3.7

Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7

OW8

OW8

OA16

OA16

IA16

Scanner Image

Not Used
Not Used
Not Used
Not Used

Not Used
Not Used

Not Used

IA16

Not Used

IA16

IA16

IA16

IA16

OW8

NIO4I

NIO4I

Not Used
Not Used

OA16

OA16

OA16

OA16

O:1.0

remote slot 1
remote slot 2
remote slot 3
remote slot 4

remote slot 5

remote slot 6

Advertising