1747-asb module 2 configuration details -20 – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 124

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

8-20 Application Examples

1747-ASB Module 2 Configuration Details

Because the image of 1747-ASB module 2 does not cross a logical rack
boundary, 1747-ASB module 2 appears as one logical device to the
scanner.

1747-ASB module 2 is configured for last chassis because it has the
highest logical group (group 5) in its highest numbered logical rack
(logical rack 3).

1747-ASB module 2 is not configured for hold last state and processor
restart lockout. If the RIO communications cable is removed and
reconnected during normal RIO communications, the discrete outputs
are reset and the 1747-ASB module automatically resumes
communicating with the PLC-5/40.

1747-ASB module 2 is configured as a complementary chassis.
Because complementary I/O is not being used, there is no need for a
primary chassis.

The 1747-ASB module 2 response time is unrestricted because the
PLC-5/40 does not require a restricted response time.

PLC Processor Input Image

PLC Processor Output Image

Bit Number

Octal

0

7

10

17

Bit Number

Octal

0

7

10

17

Logical

Rack 3

I:030
I:031
I:032
I:033
I:034
I:035
I:036
I:037

Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7

Logical

Rack 3

O:030
O:031
O:032
O:033
O:034
O:035
O:036
O:037

Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7

1747-ASB
Module 2

Not Used
Not Used

NO4I

NO4I

NO4I

NO4I

NO4I

NO4I

NO4I

NO4I

1747-ASB
Module 2

Not Used
Not Used

NIO4I

NIO4I

NIO4I

NIO4I

NIO4I

NIO4I

NIO4I

NIO4I

NI4

NI4

NI4

NI4

NI4

NI4

NI4

NI4

Advertising