2-4 Quick Start for Experienced Users
5.
Insert the 1747-ASB module into the chassis.
Reference
Chapter 5
(Installation and
Wiring)
Make sure system power is off; then insert the adapter module into slot 0 of your 1746
chassis.
ATTENTION
!
Never insert, remove or wire modules with power
applied to the chassis or devices wired to the
module.
Card Guide
Module Release
6.
Connect all RIO link devices.
Reference
Ensure that you:
•
Daisy chain each RIO link device.
•
Ground the shield drain wire to the nearest chassis mounting bolt.
•
Connect the appropriate termination resistors on each end of the link.
Important: Do not connect anything to the NC (No Connect) terminal.
Chapter 5
(Installation and
Wiring)