Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 32

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

2-4 Quick Start for Experienced Users

5.

Insert the 1747-ASB module into the chassis.

Reference

Chapter 5
(Installation and
Wiring)

Make sure system power is off; then insert the adapter module into slot 0 of your 1746
chassis.

ATTENTION

!

Never insert, remove or wire modules with power
applied to the chassis or devices wired to the
module.

Card Guide

Module Release

6.

Connect all RIO link devices.

Reference

Ensure that you:

Daisy chain each RIO link device.

Ground the shield drain wire to the nearest chassis mounting bolt.

Connect the appropriate termination resistors on each end of the link.

Important: Do not connect anything to the NC (No Connect) terminal.

Chapter 5
(Installation and
Wiring)

Advertising