Slot addressing with six slots available, 1/2-slot addressing with ten slots available, Slot addressing with nine slots available – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 66

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

4-12 Configuration

The following examples illustrate how the selection of the 1747-ASB
image size is determined by:

the addressing mode (2-slot, 1-slot, 1/2-slot)

the number of chassis slots required

4

1

2

3

456

7

8

SW1

SW2

SW3

1

23

5
6

7

8

1
23

4
5
6

7

8

O

N

O

N

O

N

Specialty I/O Mode
I/O Module Keying

Addressing Mode

Last Chassis/PLC-3 Backup

Link Response

Processor Restart Lockout

Hold Last State

Baud Rate

Primary/Complementary Chassis

ASB Module Image Size

Logical Group Number

Logical Rack Number

ON

OFF

Reserved

Using 1-slot addressing and a 7-slot chassis, six
slots are available for I/O modules. To map all
six slots into the scanner image, the 1747-ASB
module image size must be 6 logical groups.

1-Slot Addressing With Six Slots Available

1747-ASB Module

0

1

2

3

4

5

6

Slot Number

Group 0

Group 1

Group 2

Group 3

Group 4

Group 5

1747-ASB Module

0

1

2

3

4

5

6

Slot Number

Group 0,1

Group 2,3

Group 4,5

Group 6,7

Group 8,9

Group 10,1

1

7

8

9

Group 12,13

Group 14,15

Group 16,17

10

Group 18,19

Using 1/2-slot addressing and a 4-slot chassis
attached to a 7-slot chassis, ten slots are
available for I/O modules. To map all ten slots
into the scanner image, the 1747-ASB module
image size must be 20 logical groups.

If an image size of 16 logical groups is
chosen, slots 9 and 10 are unused. If an I/O
module is installed in slots 9 or 10, the
1747-ASB module ignores it unless the I/O
module faults.

1/2-Slot Addressing With Ten Slots Available

Using 2-slot addressing and a 10-slot chassis,
nine slots are available for I/O modules.

Selecting 4 logical groups leaves slot 9 unused.
If an I/O module is in slot 9, the 1747-ASB
module ignores it, unless the I/O module faults.

Selecting 6 logical groups leaves an unused
logical group in the 1747-ASB module image.
The image normally assigned to slot 10 can be
used by slot 9 (providing one full word).

2-Slot Addressing With Nine Slots Available

0

1

2

3

4

5

6

Slot Number

Group 0

Group 1

Group 2

Group 3

Group 4

7

8

9

0

1

2

3

4

5

6

Slot Number

Group 0

Group 1

Group 2

Group 3

7

8

9

1747-ASB Module

1747-ASB Module

4 Logical Groups

6 Logical Groups

Group 5

Advertising