Specifications A-7

Discrete I/O Throughput without Block Transfers Present Example

A PLC 5/40 is controlling an RIO link running at 115.2K baud that has
the following adapters:

One 1747-ASB module configured as 1/2 logical rack with 1-slot
addressing and discrete specialty I/O mode

slot 1 - 1746-IB16, 16-point input module

slot 2 - 1746-OB16, 16-point output module

slot 3 - 1746-NIO4I, 2 input/ 2 output analog module

Two adapters, each configured as a full logical rack

Three adapters, each configured as a 1/4 logical rack

1. Use the throughput formula to calculate the maximum

throughput.

T

dm-nbt

= 2T

ps

+ 2T

RIO

+ 2T

bp

+ T

SNo

+ T

SNi

+ T

id

+ T

od

+ 10ms

(1)

T

dm-nbt

= The maximum 1747-ASB module discrete throughput

without block transfers in milliseconds (ms)

T

ps

= 25.0 ms, which is from the PLC 5/40 programming manual

T

RIO

= The total RIO scan time (ms)

T

bp

= 1747-ASB module backplane scan time (ms)

T

SNo

= 0 since you are using a PLC processor with a built in scanner

T

SNi

= 0 since you are using a PLC processor with a built in scanner

T

id

= 10.0 ms, which is from I/O module instruction sheets

T

od

= 1.0 ms, which is from I/O module instruction sheets

T

dm-nbt

= 2(25) + 2T

RIO

+ 2T

bp

+ 0 + 0

+ 10.0 + 1.0

+ 10ms

(1)

2. Since there are two unknown values, continue with steps three

through seven on the following page.

3. Calculate the 1747-ASB module backplane scan time (T

bp

).

Determine the backplane scan time for each module in slots
one, two, and three.

slot 1 - 1747-IB16, 16-point input module = 0.325ms

slot 2 - 1747-OB16, 16-point output module = 0.273ms

slot 3 - 1746-NIO4I, 2 input/ 2 output analog module = input =

0.625ms output = .620ms

(2)

(1) The value of 10 ms is for PLC-5/11, -5/20, -5/30, -5/40, and -5/60 processors only. For all other PLC-5

processors the value is not required.

(2) Since the 1746-NIO4I has both input and output image, each amount is needed to calculate base backplane

scan time (T

b

).