Publication 1747-UM006B-EN-P - June 2003

3-4 Addressing

2-Slot Addressing

When the 1747-ASB module is configured for 2-slot addressing, the
processor addresses two chassis slots as one logical group. Each slot,
beginning with slot 1, is sequentially assigned one byte (8 bits) of the
1747-ASB module's input and output image. Each terminal on a
discrete I/O module installed in a slot is assigned a bit within the byte,
beginning with the least significant bit. 2-slot addressing is designed
to accommodate I/O modules whose image size is one byte or less.

Slot 1

Slot 1 is assigned to the low byte of the first logical
group of the 1747-ASB module ’s image, beginning
with bit 0 (the LSB).

Slot 1

1 5 1 4 1 3 1 2 11 1 0

9

8

7

6

5

4

3

2

1

0

Slot 2 is assigned to the high byte of the first
logical group of the 1747-ASB module ’s
image, beginning with bit 8 decimal, 10 octal.

Slot 2

1 5 1 4 1 3 1 2 11 1 0

9

8

7

6

5

4

3

2

1

0

Slot 2

Each terminal is assigned a bit,
beginning with the least significant bit.

Each terminal is assigned a bit,
beginning with the least significant bit.

group 0

group 0

Slot 1

1 5 1 4 1 3 1 2 11 1 0

9

8

7

6

5

4

3

2

1

0

Slot 2

1 5 1 4 1 3 1 2 11 1 0

9

8

7

6

5

4

3

2

1

0

Each terminal is assigned a bit,
beginning with the least significant bit.

group 0

group 0

Each terminal is assigned a bit,
beginning with the least significant bit.

Decimal

Octal

Decimal

Octal

7

0

7

0

7

0

7

0

10

10

10

10

17

17

17

17

Input Image

Input Image

Output Image

Output Image

Decimal

Octal

Decimal

Octal