Baud rate (sw2-1,2), Logical group number (sw1-7,8), Dip switch sw2 – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 58

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

4-4 Configuration

Logical Group Number (SW1-7,8)

SW1 switches 7 and 8 determine the starting logical group.

Valid starting logical group numbers are determined by the:

addressing mode (2-slot, 1-slot, or 1/2-slot)

specialty I/O mode (discrete or block transfer)

The default position is logical group zero as shipped from the factory.

If an invalid starting logical group number is selected, an error occurs.

DIP Switch SW2

Baud Rate (SW2-1,2)

SW2 switches 1 and 2 determine the baud rate the 1747-ASB module
operates at while communi cating across the RIO link.

The default is 57.6K as shipped from the factory.

4

1

23

4
5
6

7

8

SW1

SW2

SW3

1

23

5
6

7

8

1
23

4
5
6

7

8

O

N

O

N

O

N

Specialty I/O Mode
I/O Module Keying

Addressing Mode

Last Chassis/PLC-3 Backup

Link Response

Processor Restart Lockout

Hold Last State

Baud Rate

Primary/Complementary Chassis

ASB Module Image Size

Logical Group Number

Logical Rack Number

ON

OFF

Reserved

Addressing Mode

Specialty I/O Mode

Valid Starting Logical
Groups

2-slot, 1-slot, 1/2-slot

Block Transfer

0, 2, 4, 6

2-slot, 1-slot

Discrete

0, 2, 4, 6

1/2-slot

Discrete

0, 4

5

23

4

5
6

7

8

SW1

O

N

1

23

4

6

7

8

SW1

O

N

Group 0

Group 2

1

23

4

5
6

7

8

SW1

O

N

Group 4

1

23

4

5
6

7

8

SW1

O

N

Group 6

5

1 1

Baud Rate

Maximum Cable Distance (Belden 9463)

57.6K baud

3048 meters (10,000 feet)

115.2K baud

1524 meters (5,000 feet)

230.4K baud

762 meters (2,500 feet)