Publication 1747-UM006B-EN-P - June 2003

Configuration 4-11

IMPORTANT

If after assigning your 1747-ASB module image size,
you exceed logical rack 62 in complementary mode
(SW2 switch 3) or logical rack 7 in primary mode (SW2
switch 3), an error occurs. When assigning the starting
logical rack and group numbers, make sure the size of
the 1747-ASB module image does not exceed the
maximum logical rack number, as shown below:

Group 6

Group 7

Group 2

Group 3

Group 0

Group 1

Group 6

Group 4

Group 5

Group 1

Group 2

Group 7

Group 0

Group 5

Group 3

Group 4

Group 5

Group 6

Group 3

Group 4

Group 1

Group 2

Group 7

Group 0

Logical

Rack 60

Logical

Rack 61

Logical

Rack 62

Complementary Mode

Group 6

Group 7

Group 2

Group 3

Group 0

Group 1

Group 6

Group 4

Group 5

Group 1

Group 2

Group 7

Group 0

Group 5

Group 3

Group 4

Group 5

Group 6

Group 3

Group 4

Group 1

Group 2

Group 7

Group 0

Logical

Rack 5

Logical

Rack 6

Logical

Rack 7

Primary Mode

Group 7

Group 5

Group 6

Group 3

Group 4

Group 1

Group 2

Group 0

Logical

Rack 4

Group 7

Group 5

Group 6

Group 3

Group 4

Group 1

Group 2

Group 0

Logical

Rack 59

Bit Number (Decimal)

0

7

8

15

Bit Number (Octal)

0

7

17

10

Bit Number (Decimal)

0

7

8

15

Bit Number (Octal)

0

7

17

10

If you have selected logical rack 60, group
0 as your starting address, the largest
1747-ASB module image size you can
create is 24 groups (3 logical racks).
Assigning a larger 1747-ASB module
image size exceeds the maximum logical
rack number.

If you have selected logical rack 5, group 0
as your starting address, the largest
1747-ASB module image size you can
create is 24 groups (3 logical racks).
Assigning a larger 1747-ASB module image
size exceeds the maximum logical rack
number.